Also detected, no federal limit: PFBS.
Is there PFAS in Powdersville Water District (sc0420002) water?
Yes, at low levels. 1 PFAS was detected, all below EPA's 2024 limits.
Powdersville Water District (sc0420002) is a public water system drawing on surface water, based in Powdersville, South Carolina, serving about 34,960 people, including Greenville, Anderson, Easley, Liberty, Piedmont, Williamston. Under EPA's Fifth Unregulated Contaminant Monitoring Rule it was tested for 29 PFAS and lithium 8 times across 2 sampling points between Nov 2024 and Jun 2025.
Every PFAS detected
| PFAS | Detected | Highest | Worst point avg | EPA limit |
|---|---|---|---|---|
| PFBS Perfluorobutanesulfonic acid |
4 of 8 | 3.8 ppt | 3.7 ppt | none |
Not detected: HFPO-DA, PFBA, 6:2 FTS, 4:2 FTS, 8:2 FTS, ADONA, PFMPA, PFPeA, PFMBA, 9Cl-PF3ONS, NFDHA, PFDoA, PFPeS, PFHpS, PFEESA, PFOS, PFHpA, PFTrDA, PFNA, 11Cl-PF3OUdS, PFOA, PFDA, PFTA, NEtFOSAA, NMeFOSAA, PFHxA, PFUnA, PFHxS.
Lithium, tested in the same program: not detected.
What the EPA limits mean here
In April 2024 EPA set enforceable limits of 4 ppt for PFOA and PFOS, 10 ppt each for PFHxS, PFNA and GenX, and a hazard index of 1 for mixtures. Utilities were given until 2029 to comply. In May 2026 EPA proposed keeping only the PFOA and PFOS limits and moving that deadline to 2031. Until that proposal is final, the 2024 limits stand.
Compliance is judged on a running annual average at each entry point, so we show the average at this system's worst sampling point next to its single highest result. UCMR 5 results do not by themselves put a utility in or out of compliance.
What you can do at home
Levels here are under EPA's limits, so no treatment is required. If you want them lower anyway, a certified reverse osmosis system under the sink handles drinking water, and a whole-house carbon filter also takes out the chlorine or chloramine your utility adds.
Other systems in South Carolina
- West Columbia City of (3210004) above an EPA limit
- Easley Combined Util (sc3910002) none detected
- Woodruff Roebuck W/d (4220007) 4 PFAS detected
- Electric City Utilities (0410012) 1 PFAS detected
- Fort Jackson (4010501) above an EPA limit
- York County East WD (4620002) 2 PFAS detected
All 165 tested systems in South Carolina
ZIP codes served
29611 29621 29640 29642 29657 29673 29697
As reported by the utility to EPA. Neighbouring ZIPs are often split between systems; your water bill names yours.
Cite this page
Well & Tap. "PFAS in Powdersville Water District (sc0420002) water: EPA UCMR 5 results." Data: U.S. EPA Fifth Unregulated Contaminant Monitoring Rule, final release August 2026, PWSID SC0420002. https://wellandtap.com/pfas/south-carolina/powdersville-water-district-sc0420002/
About this data
Source: U.S. EPA, UCMR 5 occurrence data, final release August 2026 (PWSID SC0420002). Population: EPA SDWIS. Averages count results below the reporting level as zero, the same convention EPA uses for running annual averages. Full method.