Is there PFAS in Joint Base Anacostia - Bolling water?

Yes, at low levels. 2 PFAS were detected, all below EPA's 2024 limits.

Joint Base Anacostia - Bolling Serves 19,312 people · 16 PFOA samples from 4 sampling points · Mar 2023 to Dec 2023 PFAS found, below EPA limits
PFOA Perfluorooctanoic acid not detected
EPA 4
PFOS Perfluorooctanesulfonic acid not detected
EPA 4

Also detected, no federal limit: PFPeA, PFHxA.

Averages are for the worst sampling point, with non-detects counted as zero. Source: EPA UCMR 5.

Joint Base Anacostia - Bolling is a public water system drawing on surface water, based in Washington, District of Columbia, serving about 19,312 people. Under EPA's Fifth Unregulated Contaminant Monitoring Rule it was tested for 29 PFAS and lithium 16 times across 4 sampling points between Mar 2023 and Dec 2023.

Every PFAS detected

PFAS Detected Highest Worst point avg EPA limit
PFPeA
Perfluoropentanoic acid
7 of 16 5.6 ppt 2.5 ppt none
PFHxA
Perfluorohexanoic acid
7 of 16 5.2 ppt 2.2 ppt none

Not detected: PFHpA, ADONA, 9Cl-PF3ONS, 11Cl-PF3OUdS, PFUnA, PFDoA, PFDA, PFOA, PFOS, HFPO-DA, PFHxS, PFHpS, PFNA, PFBA, 6:2 FTS, 4:2 FTS, 8:2 FTS, PFMPA, PFPeS, PFTA, PFTrDA, NEtFOSAA, NMeFOSAA, PFMBA, PFBS, PFEESA, NFDHA.

Lithium, tested in the same program: not detected.

What the EPA limits mean here

In April 2024 EPA set enforceable limits of 4 ppt for PFOA and PFOS, 10 ppt each for PFHxS, PFNA and GenX, and a hazard index of 1 for mixtures. Utilities were given until 2029 to comply. In May 2026 EPA proposed keeping only the PFOA and PFOS limits and moving that deadline to 2031. Until that proposal is final, the 2024 limits stand.

Compliance is judged on a running annual average at each entry point, so we show the average at this system's worst sampling point next to its single highest result. UCMR 5 results do not by themselves put a utility in or out of compliance.

What you can do at home

Levels here are under EPA's limits, so no treatment is required. If you want them lower anyway, a certified reverse osmosis system under the sink handles drinking water, and a whole-house carbon filter also takes out the chlorine or chloramine your utility adds.

Other systems in District of Columbia

All 3 tested systems in District of Columbia

ZIP codes served

20032

As reported by the utility to EPA. Neighbouring ZIPs are often split between systems; your water bill names yours.

Cite this page

Well & Tap. "PFAS in Joint Base Anacostia - Bolling water: EPA UCMR 5 results." Data: U.S. EPA Fifth Unregulated Contaminant Monitoring Rule, final release August 2026, PWSID DC0000004. https://wellandtap.com/pfas/district-of-columbia/joint-base-anacostia-bolling/

About this data

Source: U.S. EPA, UCMR 5 occurrence data, final release August 2026 (PWSID DC0000004). Population: EPA SDWIS. Averages count results below the reporting level as zero, the same convention EPA uses for running annual averages. Full method.